Hardware, Engineering and Function DescriptionXControl PLC SystemXC-POW50(-XION)-UPS Base ModuleXC-ADP(-XION) Power Supply ModuleXC-NET-CAN CANopen Mo
Hardware and Engineering12/01 AWB2700-1428GB8Fitting XI/ON base modulesThe XI/ON base modules are fitted on the right of the XC600 controller on the m
12/01 AWB2700-1428GBEngineering9VentilationA minimum gap of 5 cm between passive components must be provided in order to ensure sufficient ventilation
Hardware and Engineering12/01 AWB2700-1428GB10Wiring example (overview)Switching the power supply on/offThe UPS ensures that the XC600 controller is s
12/01 AWB2700-1428GBXC-ADP/XC-ADP-XION base modules11These functions were implemented by adapting the UPS device supplied by Konzept to the power supp
Hardware and Engineering12/01 AWB2700-1428GB12Expansion with XI/ON modulesThe following XI/ON base modules can be connected directly to the XC-ADP-XIO
12/01 AWB2700-1428GBXC-NET-DP-M PROFIBUS-DP module13The PROFIBUS-DP module can be fitted between the power supply module and the CPU module. Engineeri
Hardware and Engineering12/01 AWB2700-1428GB14X Assign the memory range beginning with start address CE000 to the first module (CANopen or PROFIBUS-DP
12/01 AWB2700-1428GBXC-NET-CAN CANopen module15Assign the input/output address range (%IB/%QB) to the module in the PLC configuration in XSoft:The mod
Hardware and Engineering12/01 AWB2700-1428GB16XC-SYS1 operator moduleThe operator module always forms the final component of several stacked modules,
12/01 AWB2700-1428GBXC-CPU601-E.M processor17The following table shows the reaction of the PLC when the oper-ating mode selector switch is changed. Re
IBefore commencing the installation• Disconnect the power supply of the device.• Ensure that devices cannot be accidentally restarted.• Verify isolati
12/01 AWB2700-1428GB18
12/01 AWB2700-1428GB192 Establishing the Connection Between PC and XC600This section describes the necessary steps for connecting the PC to the XC600
Establishing the Connection Between PC and XC60012/01 AWB2700-1428GB20Configuring the XC600Assign the IP address and the Subnet Mask to the PLC:X Use
12/01 AWB2700-1428GBCreating the connection between PC and XC60021After confirming the entry, the name will appear in the Channels column.X Confirm th
12/01 AWB2700-1428GB22
12/01 AWB2700-1428GB233 Creating an Example ProjectThe following example is used to illustrate the use of the XSoft software. A project is created by
Creating an Example Project12/01 AWB2700-1428GB24Setting the target systemOnce XSoft has started, create a new file:X Choose File r New.X Answer the q
12/01 AWB2700-1428GBConfiguring the XC600 controller25Configuring the XC600 controllerX Click the Resources tab to configure the XC600 with local inpu
Creating an Example Project12/01 AWB2700-1428GB26X Select the Input/Output tab to configure the inputs and outputs.X Select the required input/output
12/01 AWB2700-1428GBConfiguring the XC600 controller27Creating programsTask The first input of each XI/ON module is to be interrogated. Both inputs ar
12/01 AWB2700-1428GB1About This Manual 3Structure 3Abbreviations and symbols 31 Hardware and Engineering 5Setup 5Mounting 6– Fitting/removing modules
Creating an Example Project12/01 AWB2700-1428GB28PROFIBUS-DP expansionProceed as follows to expand the configuration with remote I/Os via PROFIBUS-DP:
12/01 AWB2700-1428GBPROFIBUS-DP expansion29X Choose Tools -> Compute Address to specify the addresses.Creating a program for PROFIBUS-DP expansionT
Creating an Example Project12/01 AWB2700-1428GB30The example is saved as a separate program and is called from the program ABC. Proceed as follows to
12/01 AWB2700-1428GBCANopen bus expansion31X To configure the output module select the element XC-NET-CAN and right-click it. Choose Append Subelement
Creating an Example Project12/01 AWB2700-1428GB32Creating a program for remote outputs on the CANopen busThe following two output bytes are provided.
12/01 AWB2700-1428GB334 Functions of the Operator ModuleThis chapter describes the operation of the PLC via the operator module. An example of commiss
12/01 AWB2700-1428GB34Starting up the PLC with a bootable and activated programAfter each startup, the activation of menu item LOAD or REBOOT, the PLC
12/01 AWB2700-1428GB35Starting programs The CPU will process the executable program after the startup. The program can be started in the following way
Functions of the Operator Module12/01 AWB2700-1428GB36Startup with configuration scanOn startup the PLC system always scans the modules of which the P
12/01 AWB2700-1428GBGeneral messages37General messagesDeleting programs from the hard diskRequirement: a bootable version of the program is on the har
Contents12/01 AWB2700-1428GB23 Creating an Example Project 23Setting the target system 24Configuring the XC600 controller 25– Creating programs 27PROF
Functions of the Operator Module12/01 AWB2700-1428GB38This change will show that the function has been completed.Handling several programsSeveral boot
12/01 AWB2700-1428GBPassword39PasswordThe password ensures that access to the XC600 PLC is controlled.Entering passwords X Use the MSS to choose MAIN
Functions of the Operator Module12/01 AWB2700-1428GB40Shutting down the system X Use the MSS to choose MAIN MENU r SYSTEM r SHUTDOWN and press the MSS
12/01 AWB2700-1428GB415 Menu Overview of the Operator ModuleThe operator module allows you to enter parameters or modify PLC states. The display has f
Menu Overview of the Oper-ator Module12/01 AWB2700-1428GB42Basic menuAfter the power supply is switched on or after a reboot, the display shows messag
12/01 AWB2700-1428GBBasic menu43MAIN MENU: PROGRAMRESETThis menu contains different Reset functions:All of these Reset commands switch the PLC to STOP
Menu Overview of the Oper-ator Module12/01 AWB2700-1428GB44MAIN MENU: RECIPEThe menu structure of the of the recipe menu is the same as the structure
12/01 AWB2700-1428GBBasic menu45After a power failure, the PLC will start up in the mode specified by the OMS setting when the password was activated,
Menu Overview of the Oper-ator Module12/01 AWB2700-1428GB46HARDWARECONFIGURE: After the CONFIGURE menu is called, the display shows the current module
12/01 AWB2700-1428GB47AppendixOther error messagesTask monitoringBus errorChecksum errorFieldbus errorI/O update errorCycle time exceededInvalid instr
12/01 AWB2700-1428GB3About This ManualStructureThe XC600 PLC is designed for the control of machines and systems. This controller provides the basis f
Appendix12/01 AWB2700-1428GB48Technical DataXControlGeneralStandards and regulations IEC/EN 61131-2, EN 50178Ambient temperature0 to +55 °CStorage tem
12/01 AWB2700-1428GBTechnical Data49Operator module XC-SYS1LCD display 4 lines x 12 columnsRTC (real time clock)YesBattery (Lithium)XC-CPU-BAT1Compact
Appendix12/01 AWB2700-1428GB50Power supply module XC-POW50-XION-UPS (with XI/ON) XC-POW50-UPS (without XI/ON)Rated input voltage 24 V DC +20/–15 % 24
12/01 AWB2700-1428GB51IndexA Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3Adding modules . . . . . . . . . . . .
Index12/01 AWB2700-1428GB52M MAIN MENU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42Menu selector switch . . . . . . . . . . .
12/01 AWB2700-1428GB4
12/01 AWB2700-1428GB51 Hardware and EngineeringSetupThe XC600 PLC has a modular design. The basic unit consisting of the base, power supply, CPU and o
Hardware and Engineering12/01 AWB2700-1428GB6A maximum of three bus modules for PROFIBUS-DP and CANopen can be fitted between the power supply and CPU
12/01 AWB2700-1428GBMounting7Figure 4: Removing the base moduleFigure 5: Detaching the modules10121